Topologies of SIMATIC NET PROFIBUS Networks

2-27

PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000

Rules

The following rules must be taken into account when extending PROFIBUS-PA:

S

There can be a maximum of 31 PA field devices in a PROFIBUS-PA system

S

Only one device supplying power (=DP/PA coupler) can be connected in a
physical PROFIBUS-PA segment.

S

A maximum of 31 PA field devices can be attached to a DP/PA link. The
maximum number of attachable PA field devices per physical PROFIBUS-PA
segment or per DP/PA coupler is limited by the maximum output current of the
DP/PA coupler and the I/O data to be transferred.