beautypg.com

Siemens SIMATIC NET PROFIBUS User Manual

Page 462

background image

Technical Specifications

7-2

PROFIBUS Optical Bus Terminal (OBT)

C79000-G8976-C122-02

Wavelength

640 nm to 660 nm

Permitted FO cable attenuation
(with link power margin)

– for plastic fiber 980/1000

– for PCF fiber 200/230

13 dB

3 dB

Transmission distance with 3dB link power margin

– with plastic fiber 980/1000

with max. 200 dB/km cable attenuation

– for PCF fiber 200/230

with max. 10 dB/km cable attenuation

0.1m to 50m

0 m to 300m

FO connector

Simplex / duplex

Electromagnetic compatibility (EMC)

Noise emission

Limit class A (EN 55022)

Immunity to static discharge

On shield connection and casing:

±

6 kV contact di-

scharge (IEC 1000–4–2)

Immunity to high frequency interference

10 V/m at 80% amplitude modulation at 1kHz,

80MHz – 1GHz (ENV 50140; IEC 61000–4–3)

10V/m at 50% on time at 900MHz

(ENV 50 204)

10 V/m at 80% amplitude modulation at 1kHz,

10kHz – 80MHz (ENV 50141)

Immunity to conducted interference

(burst)

On power supply cables and shielded RS 485 LAN
cables:

±

2 kV

(IEC 61000–4–4)

Immunity to conducted interference

(surge)

On power supply cables:

±

1 kV balanced

On shielded RS 485 LAN cables:

±

2 kV unbalanced

(IEC 61000–4–5)

Safety

VDE requirements

VDE 0806=EN60950 and IEC950

UL/CSA approval

complying with UL1950/CSA950

Climatic conditions

Ambient temperature

0

°

C to +60

°

C

(IEC 68–2–1, IEC 68–2–2)

Storage temperature

-40

°

C to +70

°

C

(IEC 68–2–14)