Help With Problems During Operation

10.1

Status Displays for Incorrect Operation

LED Display

Possible Causes

Signaling
Contact

POWER LED

not lit

-

Power supply failed or turned off

-

Module defective

-

Ribbon band cable not plugged in when assem-
bling the module

Always si-
gnals

POWER LED

lit green

TX LED

not lit

RX LED

not lit

-

Interruption on one or more cores of the RS 485
LAN cable

-

Reversed connection of core A and B of the RS
485 LAN cable

-

Connected PROFIBUS master defective (not sen-
ding)

-

PROFIBUS node is not attached or attached
PROFIBUS node is not turned on

-

No partner station detected with attached PROFI-
BUS master

POWER LED

lit green

TX LED

not lit

RX LED

lit yellow

-

Interruption on one or more cores of the RS 485
LAN cable

-

Reversed connection of core A and B of the RS
485 LAN cable

-

Attached PROFIBUS slave defective (not sen-
ding)

-

PROFIBUS slave is not attached or attached
PROFIBUS slave is not turned on

-

PROFIBUS slave node not correctly addressed
and therefore not responding

POWER LED

lit green

TX LED

lit orange,

RX LED

not lit

-

No acknowledgment pulse received, partner sta-
tion not responding

Signals when
configured
(acknowledg-
ment pulse)