Active Components for RS-485 Networks

5-3

PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000

Table 5-1

Description and Functions of the RS-485 Repeater

Layout of the Repeater

No.

Function

DC
24 V

L+ M PE M 5.2

А

10

А

Terminal for connecting the power supply of the RS 485
repeater (pin “M5.2” is the reference ground if you want to
measure the voltage between terminals “A2” and “B2”).

24 V

А

Б

10

Б

Shield clamp for strain relief and grounding the LAN cable of
bus segment 1 or bus segment 2

В

В

Terminal for the LAN cable of bus segment 1

Â

A1

B1

A1

B1

Ã

Terminating resistor for bus segment 1 )

1

Г

Д

И

A1

B1

A1

B1

PG

11

OFF

ON

DP1

Ä

Switch for OFF state

(= Disconnect bus segments 1 and 2, for example, during
commissioning)

Å

OP

DP2

12

Å

Terminating resistor for bus segment 2 )

1

SIEMENS

ON

Æ

Terminal for the LAN cable of bus segment 2

SIEMENS

RS 485-REPEATER

Æ

A2

B2 A2

B2

Ç

Catch for mounting and removing the RS-485 repeater on a
standard rail

Б

И

Interface for PG/OP on bus segment 1

Á

10

LED 24 V power supply

Ç

11

LED indicating bus activity on segment 1

12

LED indicating bus activity on segment 2

)

1

If the terminating resistor is activated, the right-hand bus attachment is disconnected (see

Figure 5-3) !

Note

Terminal M5.2 of the power supply (see Table 5-1, no.

À

) is used as the reference

ground for signal measurements if problems occur and must not be wired up.