Siemens SIMATIC NET PROFIBUS User Manual
Page 212
Passive Components for Electrical Networks
7-16
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Table 7-5
Technical Specifications of the Flexible Fiber-Optic Trailing Cable and the SIENOPYR Duplex
Fiber-Optic Marine Cable
Cable Type
SIENOPYR
Duplex Fiber-Optic
Marine Cable
Flexible Fiber-Optic
Trailing Cable
Strain relief
GFK central element, Aramid
yarn
Aramid yarn
Outer jacket/color of cable
PUR, black
SHF1 mixture/black
Dimensions Basic element
(3.5
±
0.2) mm
∅
(2.9
±
0.2) mm
∅
Outer dimensions
approx. 12.9 mm
(13.3
±
0.5) mm
Cable weight
approx. 136 kg/km
approx. 220 kg/km
Permitted tensile load
<= 2000 N (brief)
<=1000 N (permanent)
<= 500 N (brief)
<= 250 N (permanent)
Bending radii
150 mm
Max. 100,000 bending cycles
133 mm (single)
266 mm (multiple)
Installation temperature
-5
°
C to +50
°
C
-10
°
C to +50
°
C
Operating temperature
-25
°
C to +60
°
C
-40
°
C to +80
°
C 1)
-40
°
C to +70
°
C 2)
Storage temperature
-25
°
C to +70
°
C
-40
°
C to +80
°
C
Resistance to fire
Complying with IEC 60332-1
Complying with IEC 60332-3 cat.
A
Free of halogens
no
yes
UL approval
no
no
Ship building approval
no
yes
1) With no load on copper cores
2) With maximum load on copper cores (6 A)