7 Technical Data

Version 1.0 8/00

OLM Module

P11

G11

G11-1300

P12

G12

G12-1300

G12-EEC

Voltage/power supply

Operating voltage

18 V to 32 V DC, typ. 24 V, (redundant inputs uncoupled),
safety extra-low voltage, indirect-coupled

Current consumption

max. 200 mA

Output voltage/current for terminal

5 V + 5%, – 10% / 90 mA; short circuit-proof

resistors (Pin 6 Sub-D socket)

Signaling contact

Maximum switch voltage

60 V DC; 42 V AC (safety extra-low voltage)

Maximum switch current

1.0 A

Signal transmission

Transmission rate

9.6; 19.2; 45.45; 93.75; 187.5; 500 kBit/s
1.5; 3; 6; 12 Mbit/s

Setting transmission rate

automatic

Bit error rate

< 10

-9

Signal processing time (any input/output)

6.5 t

Bit

Retimer

Input Port 1 to 3

Signal distortion

± 30 %

Bit length

± 0.12 %

Output Port 1 to 3

Mean bit length

± 0.01 %

Safety

VDE regulation

VDE 0806 = EN 60950 and IEC 950

UL/CSA approval

UL 1950/CSA 950

FM approval

in preparation (Class 2)

Electrical port

Input/output signal

RS 485 level

Input dielectric strength

– 10 V to + 15 V

PIN assignment, port 1

in accordance with EN 50170 Part 1

Indirect-coupled

yes, within SELV limits

Optical ports

Wavelength

660 nm

860 nm

1310 nm

Launchable optical power
– in glass fiber E 10/125

– 19 dBm

– in glass fiber G 50/125

– 15 dBm

– 17 dBm

– in glass fiber G 62.5/125

– 13 dBm

– 17 dBm

– in PCF fiber S 200/230

transmitting power ”Reduced“

transmitting power ”Default“

– 17 dBm

– in plastic fiber S 980/1000

transmitting power ”Reduced“

– 9.5 dBm

transmitting power ”Default“

– 5 dBm

Receiver sensitivity

– 25 dBm

– 28 dBm

– 29 dBm

Receiver overload

– 3 dBm

– 3 dBm

– 3 dBm