beautypg.com

Siemens SIMATIC NET PROFIBUS User Manual

Page 224

background image

Passive Components for Electrical Networks

7-28

PROFIBUS Networks SIMATIC NET

6GK1970-5CA20-0AA1 Release 2 05/2000

Cable Lengths

The length of the transmission path on fiber-optic cables is not dependent on the
transmission rate.

Each node on the optical PROFIBUS network has repeater functionality so that the
following distance information relates to the distance between two adjacent,
interconnected PROFIBUS nodes in a bus topology.

The maximum cable length between two PROFIBUS nodes depends on the type
of fiber-optic cable used.

Table 7-7

Permitted Cable Lengths in Networks with Integrated Optical Interfaces (Bus
Topology)

Fiber-optic cable

SIMATIC NET

PROFIBUS

Maximum cable

lengths between two

nodes (in m)

For 1 Network (= 32

nodes) (in m)

Plastic fiber-optic,
duplex cord

50

1550

Plastic fiber-optic,
standard cable

50

1550

PCF fiber-optic,
standard cable

300

9300

Table 7-8

Permitted Cable Lengths in an OLM Network

Fiber-optic cable

SIMATIC NET

PROFIBUS

Maximum cable

lengths between two

nodes (in m)

For 1 Network (= 32

nodes) (in m)

Plastic fiber-optic,
duplex cord

50

1550

Plastic fiber-optic,
standard cable

80

2480

PCF fiber-optic,
standard cable

400

12400