Topologies of SIMATIC NET PROFIBUS Networks

2-3

PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000

Connecting Segments Using RS-485 Repeaters

By using RS-485 repeaters, segments can be interconnected. The RS-485
repeater amplifies the data signals on the LAN cables. You require an RS-485
repeater when you want to attach more than 32 nodes to a network or when the
permitted segment length is exceeded. A maximum of 9 repeaters can be used
between any two nodes. Both bus and tree structures can be implemented.

Figure 2-1 shows a typical topology using the RS-485 technique with 3 segments
and 2 repeaters.

À

Terminating resistor activated

Á

PG attached via tap line (6ES7 901-4BD00-0XA0)

for maintenance purposes

RS-485
repeater

RS-485
repeater

А

А

А

А

А

А

S7-400

S7-300

S7-300

S7-400

S7-400

Tap line

Á

OP 25

PG

OP 25

OP 25

PG

Figure 2-1

Topology Using the RS-485 Technique

Increasing the overall span of a network by using repeaters can lead to longer
transmission times that may need to be taken into account when configuring the
network (see Chapter 3).

2.1.1

Components for Transmission Rates up to 1.5 Mbps

All SIMATIC NET bus attachment components can be used for transmission rates

1.5 Mbps.