Siemens SIMATIC NET PROFIBUS User Manual
Page 170
Active Components for RS-485 Networks
5-4
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Technical Specifications
Table 5-2 lists the technical data of the RS-485 repeater:
Table 5-2
Technical Data of the RS-485 Repeater
Technical Specifications
Power supply
S
Rated voltage
24 V DC
S
Ripple (static limit)
20.4 V DC to 28.8 V DC
Power consumption at rated voltage
S
Without load on the PG/OP connector
200 mA
S
Load on the PG/OP connector (5 V/90 mA)
230 mA
S
Load on the PG/OP connector (24 V/100 mA)
300 mA
Electrical isolation
yes, 500 V AC
Transmission rate (detected automatically by
repeater)
9.6 Kbps, 19.2 Kbps, 45.45 Kbps,
93.75 Kbps, 187.5 Kbps, 500 Kbps,
1.5 Mbps, 3 Mbps, 6 Mbps 12 Mbps
Degree of protection
IP20
Dimensions W
H
D (in mm)
45
128
67
Weight (including packing)
350 g
Pinout of the Sub D Connector (PG/OP Connector)
The 9-pin sub D connector has the following pinout:
Table 5-3
Pin Assignment of the 9-Pin Sub D Connector PG/OP Connector
Layout
Pin no.
Signal name
Meaning
1
–
–
2
M24V
Chassis 24 V
5
3
RxD/TxD-P
Data line B
9
4
4
RTS
Request To Send
3
8
5
M5V2
Data reference potential (from station)
2
7
6
P5V2
Power supply plus (from station)
2
1
6
7
P24V
24 V
1
8
RxD/TxD-N
Data line A
9
–
–