Active Components for RS-485 Networks

5-4

PROFIBUS Networks SIMATIC NET

6GK1970-5CA20-0AA1 Release 2 05/2000

Technical Specifications

Table 5-2 lists the technical data of the RS-485 repeater:

Table 5-2

Technical Data of the RS-485 Repeater

Technical Specifications

Power supply

S

Rated voltage

24 V DC

S

Ripple (static limit)

20.4 V DC to 28.8 V DC

Power consumption at rated voltage

S

Without load on the PG/OP connector

200 mA

S

Load on the PG/OP connector (5 V/90 mA)

230 mA

S

Load on the PG/OP connector (24 V/100 mA)

300 mA

Electrical isolation

yes, 500 V AC

Transmission rate (detected automatically by
repeater)

9.6 Kbps, 19.2 Kbps, 45.45 Kbps,
93.75 Kbps, 187.5 Kbps, 500 Kbps,
1.5 Mbps, 3 Mbps, 6 Mbps 12 Mbps

Degree of protection

IP20

Dimensions W

H

D (in mm)

45

128

67

Weight (including packing)

350 g

Pinout of the Sub D Connector (PG/OP Connector)

The 9-pin sub D connector has the following pinout:

Table 5-3

Pin Assignment of the 9-Pin Sub D Connector PG/OP Connector

Layout

Pin no.

Signal name

Meaning

1

2

M24V

Chassis 24 V

5

3

RxD/TxD-P

Data line B

9

4

4

RTS

Request To Send

3

8

5

M5V2

Data reference potential (from station)

2

7

6

P5V2

Power supply plus (from station)

2

1

6

7

P24V

24 V

1

8

RxD/TxD-N

Data line A

9