26

5 LED Indicators and Troubleshooting

Version 1.0 8/00

Possible causes

Signals are being received on the RS 485 bus line

– Bus subscriber is not connected
– Connected bus subscriber is not switched on
– One or both conductors in the RS 485 bus line is broken

Sporadic interference signals because
– the RS 485 bus line being insufficiently shielded
– an open RS 485 bus line, i.e. it is only connected to the module at one end
– the RS 485 segment is not terminated or only terminated at one end
– an RS 485 bus terminal or terminal connector has been plugged in/ pulled out
Permanent interference because
– conductors A and B in the RS 485 bus line have been transposed
– of an RS 485 bus line short circuit
– the send time has been exceeded caused by a bus subscriber in a bus

segment connected to Port 1

– module and another bus subscriber connected via Port 1 are both sending at

the same time (e.g. because an address has been assigned twice, the setting
of the slot time is too low, or during lifting of the segmentation in the optical
line, see Chap. 3.1.1)

– RS 485 driver of the module is defective (e.g. after lightning strike)

PROFIBUS frames are being received at the optical port

Operating mode ”Line with optical fiber link monitoring“ and

”Redundant optical ring“

Transmission rate has not yet been recognized – LED ”System“ flashes red
– No transmitting bus subscriber present
– Send and receive optical fibers have been transposed
– No partner module connected or partner module is not switched on
– Connected partner module is defective

Transmission rate has been recognized - LED ”System“ flashes green
– If the operating mode ”Redundant optical ring“ has been set, the optical port

works as a stand-by port. There is no malfunction in the OLM or the optical
fiber.

– If one of the operating modes ”Line with optical fiber link monitoring …“ has

been set, no PROFIBUS frames are received at the optical port. There is no
malfunction in the OLM or the optical fiber.

Transmission rate has been recognized – LED ”System“ lights green or
flashes red/green
– No transmitting bus subscriber present (optical fiber connection is OK)

– Send and receive optical fibers have been transposed
– No partner module connected or partner module is not switched on
– Connected partner module is defective
– Send time of connected partner module has been exceeded
– An optical fiber line is broken
– Optical fiber link to partner module is too long
– Loose connection in an optical fiber connector
– Optical fiber in the optical fiber connector is loose
– When using a redundant optical ring: if a fault in the optical fiber has been

corrected but the port LEDs on both of the OLMs concerned still light red,
check whether parameter HSA has been set as described the in Chap. 3.3.

– Fault occurs periodically (see above)
– Loose connection in an optical fiber connector
– Optical fiber in the optical fiber connector is loose
– Only one active bus subscriber is connected, which only sends tokens to

itself. A fault should not be signaled as soon as a second subscriber is
activated.

Operating mode ”Line without optical fiber link monitoring“

Signals are received at the optical port.

– No transmitting bus subscriber present
– Send and receive optical fibers have been transposed
– No partner module connected or partner module is not switched on
– Connected partner module is defective

LED Indicator

CH1

lights yellow

electric

not lit

flashes/ lights red

CH2, CH3

lights yellow

optical

not lit

flashes yellow

lights red

flashes red / yellow

lights yellow

not lit

Signaling contact

no signal

no signal

signal

no signal

no signal

no signal

no signal

signal

signal

no signal

no signal

5.1 LED Indicators

Table 2: What the LED indicators and signaling contacts mean