Configuring Networks

3-3

PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000

Note

The power supply to terminating resistors must not be interrupted by turning off
the DTE or repeater or by unplugging the bus connector or tap line. If the power
supply to the terminating resistors cannot be guaranteed, the PROFIBUS
terminator must be used.

3.1.1

Segments for Transmission Rates up to a Maximum of 500 Kbps

Transmission Rates up to a Maximum of 500 Kbps

The following maximum segment lengths can be implemented with the SIMATIC
NET PROFIBUS LAN cables:

Table 3-1

Possible Segment Lengths

Segment Length for Cable Type

Transmission Rate
in Kbps

– FC Standard Cable
– FC Robust Cable
– FC FRNC Cable
– FC Food Cable
– FC Underground Cable
– SIENOPYR–FR Marine Cable

– FC Trailing Cable
– PROFIBUS Flexible Cable
– PROFIBUS Festoon Cable

9.6

1000 m

900 m

19.2

1000 m

900 m

45.45

1000 m

900 m

93.75

1000 m

900 m

187.5

1000 m

700 m

500

400 m

400 m

The maximum permitted number of bus attachments (DTEs, repeaters, OLMs,
BT12 M,...) to one segment is 32.