beautypg.com

1 point–to–point–link – Siemens SIMATIC NET PROFIBUS User Manual

Page 353

background image

Infrared Link Modul (ILM)

6ZB5530–3AC30–0BA1

11

Copyright

by Siemens

5.2.1

PointtoPointLink

Infrared
transmission link
0.5 to 15 m

PROFIBUS
master network segment

PROFIBUS
slave network segment

Slave

Master

Master

Master

Slave

Slave

Slave

ILM

ILM

Figure 2:

Point-to-Point Link with Two PROFIBUS ILMs

Figure 2 describes the typical layout of a PROFIBUS network with master and slave nodes and an infrared
transmission link with two PROFIBUS ILMs. The infrared transmission link is implemented as a point-to-point
link by the two PROFIBUS ILMs. In this situation, the two PROFIBUS ILMs replace a cable connection
between the two network segments. Remember that only slave nodes are permitted in the slave network
segments.

+

Make sure that the terminating resistors are activated at the segment ends (either in the bus
connector or in a PROFIBUS ILM).

Cascading is a further application for a point-to-point link.

Note

This “cascading with PROFIBUS ILM” mode is possible, but does involve a risk when operating PROFIBUS.
The transmission using an infrared link is generally more susceptible to problems than transmission via cable
(optical or electric).