Infrared Link Modul (ILM)

6ZB530–3AC30–0BA1

42

Copyright

by Siemens

LED Display

Possible Causes

Signaling
Contact

POWER LED

lit green

TX LED

lit orange,

RX LED

lit yellow

-

No acknowledgment pulse received since partner
station not configured with acknowledgment pulse

-

On point-to-multipoint links on the PROFIBUS
ILM of the master subnet if acknowledgment bit
configured (see Section 6.4)

Signals when
configured
(acknowledg-
ment pulse)

POWER LED

lit green

TX LED

lit orange,

RX LED

lit yellow,

LOW LED

lit red

-

No acknowledgment pulse received since partner
station is not configured with acknowledgment
pulse or receive level for acknowledgment pulse
and response frame too low.

-

On a point-to-multipoint link on the PROFIBUS
ILM on a slave subnet if configured with acknow-
ledgment bit (see Section 6.4)

Signals if

configured

(acknowledg-
ment pulse,
level monito-
ring)

POWER LED

lit green

TX LED

lit yellow

RX LED

not lit

-

Partner station not responding because not atta-
ched, infrared link interrupted, incorrectly configu-
red (PROFIBUS address of the slave incorrect,
data rate of the partner PROFIBUS ILM set incor-
rectly etc.)

Signals when
configured

(bus activity)

POWER LED

lit green

TX LED

lit yellow,

RX LED

lit yellow,

LOW LED

lit red

-

Risk of problems on bus, since infrared link has
too much attenuation (obstacles in area of trans-
mission link, distance between PROFIBUS ILMs
too great, PROFIBUS ILM turned out of line with
partner station)

Signals when
configured

(level monito-
ring)

POWER LED

lit green

TX and RX LEDs not lit

ERROR LED

lit red

-

Risk of problems on bus due to incidence of ex-
traneous light (for example sunlight, lamps with
infrared component, halogen lamps with high
energy)

Signals when
configured

(constant
light)

POWER LED

lit green

RX LED

lit yellow

ERROR LED

lit red

-

Bus problems must be expected due to incidence
of extraneous light with high-frequency modula-
tion (for example energy-saving lamps with HF
switching device)

Signals when
configured

(constant
light)

Table 1:

Possible problems operating the PROFIBUS ILM