5 grounding – Siemens SIMATIC NET PROFIBUS User Manual
Page 156
Passive Components for RS-485 Networks
4-58
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
4.7.5
Grounding
If the bus terminal is mounted on a DIN rail (see Figure 4-33), the shield clamp
makes large-area contact with the rail via an internal spring. To connect the cable
shield with local ground, a connection between the DIN rail over as short a
distance as possible to local earth is adequate.
PE
A B
A
B
PE
УУУУ
УУУУ
P
E
A B
A B
P
E
УУУУУ
УУУУУ
A B
A B
PE
УУУУУ
УУУУУ
С
С
PE
A B
A B
PE
УУУУУ
УУУУУ
С
С
СС
СС
С
С
С
С
С
С
Wall installation with securing
screws
Installation with a standard rail
on a cabinet panel
Shield clamp/
PE
grounding bar
Installation on closet panel
with securing screws
Bus
terminated
Bus
terminated
Bus
terminated
Bus
terminated
Shield clamp/
grounding bar
MADE IN GERMANY
MADE IN GERMANY
MADE IN GERMANY
MADE IN GERMANY
1)
2
)
1) If this grounding cable exceeds a length of 20 cm,
the shield must be grounded to the closet panel (2).
Figure 4-33
Ways of Installing and Grounding the Bus Terminal
Note
The grounding bar and local ground must be connected by a Cu conductor with
≥
6 mm
2
cross-section over as short a distance as possible.