Battery capacity range of lithium-ion
batteries
50 Ah to
10,000 Ah
50 Ah to
10,000 Ah
50 Ah to
10,000 Ah
50 Ah to
10,000 Ah
Recommended minimum battery
capacity C10 in systems for increased
self-consumption
100 Ah
100 Ah
100 Ah
100 Ah
Recommended minimum battery
capacity C10 in battery backup
systems
100 Ah
100 Ah
120 Ah
160 Ah
Recommended minimum battery
capacity C10 in off-grid systems
100 Ah
150 Ah
190 Ah
250 Ah
Recommended minimum battery
capacity C10 per 1,000 Wp power of
PV systems in off-grid systems
100 Ah
100 Ah
100 Ah
100 Ah
Charge control for lead-acid batteries
IUoU charging
behavior with
automatic full
charge and
equalization
charge
IUoU charging
behavior with
automatic full
charge and
equalization
charge
IUoU charging
behavior with
automatic full
charge and
equalization
charge
IUoU charging
behavior with
automatic full
charge and
equalization
charge
DC connection
Terminal lug M8,
20 mm to
25 mm wide
Terminal lug M8,
20 mm to
25 mm wide
Terminal lug M8,
20 mm to
25 mm wide
Terminal lug M8,
20 mm to
25 mm wide
Permitted conductor cross-section
50 mm² to
95 mm²*
50 mm² to
95 mm²*
50 mm² to
50 mm² to
Maximum connectable conductor
cross-section
95 mm²*
Cable diameter
14 mm to 25 mm 14 mm to 25 mm 14 mm to 25 mm 14 mm to 25 mm
Torque
12 Nm
12 Nm
12 Nm
12 Nm
* In the event of a cross-section of 95 mm², observe the maximum cable diameter.
Sunny Island
3.0M
Sunny Island
4.4M
Sunny Island
6.0H
Sunny Island
8.0H
Maximum efficiency
95.3%
95.3%
95.8%
95.8%
European weighted efficiency
94.0%
94.0%
94.3%
94.1%
Sunny Island
3.0M
Sunny Island
4.4M
Sunny Island
6.0H
Sunny Island
8.0H