beautypg.com

SMA SI 3.0-11 Installation User Manual

Page 74

background image

8  Commissioning

SMA Solar Technology AG

74

SI30M-44M-60H-80H-IA-en-30

Installation Manual

The following ranges result from the parameter default values:

The following ranges result from deactivating the seasonal adjustment with the default values of the parameters:

BURes

262.03 BUResSOC
Range for the battery backup system function
With seasonal adjustment (see Section 8.2.4.1,

page 69), the value of 262.03 BUResSOC applies

to the longest day of the year. When the seasonal

adjustment is deactivated, only the minimum range

is used and the SlfCsmp increased respectively.

The Sunny Island uses this range for supplying the

battery backup grid when the utility grid fails. When

the utility grid is available again, the battery is

charged by the Sunny Island with nominal power

from the utility grid.

BatRes

262.02 BatResSOC
Range for protection against deep discharge This

range can only be reached when the utility grid

fails.

The Sunny Island switches into standby mode. The

Sunny Island starts up every two hours and attempts

to charge the battery with PV energy. If the battery

cannot be charged, the Sunny Island switches back

to standby mode.
When the utility grid is available, the Sunny Island

charges the battery with nominal power from the

utility grid.

ProtRes

262.01 ProtResSOC
Range for protection during deep discharge
This range can only be reached when the utility grid

fails.

When this range is reached, the Sunny Island

switches off in order to protect the battery. When

the utility grid is available again, the system must be

charged manually ("Charging the Battery after Auto

Power Off", see Sunny Island operating manual).

Range

Lead-acid battery

Lithium-ion battery

Shortest day*

* December 21 (northern hemisphere) or June 21 (southern hemisphere)

Longest day**

** June 21 (northern hemisphere) or December 21 (southern hemisphere)

Shortest day*

Longest day**

SlfCsmp

65% to 100%

45% to 100%

30% to 100%

28% to 100%

PVRes

60% to 65%

40% to 45%

25% to 30%

23% to 28%

BURes

15% to 60%

15% to 40%

13% to 25%

13% to 23%

BatRes

10% to 15%

10% to 15%

3% to 13%

3% to 13%

ProtRes

0% to 10%

0% to 10%

0% to 3%

0% to 3%

Range

Lead-acid battery

Lithium-ion battery

SlfCsmp

65% to 100%

30% to 100%

PVRes

60% to 65%

25% to 30%

BURes

15% to 60%

13% to 25%

BatRes

10% to 15%

3% to 13%

ProtRes

0% to 10%

0% to 3%

Range

Parameter and explanation of the value

Behavior of the Sunny Island inverter

This manual is related to the following products: