SMA Solar Technology AG

5  Product Description

Installation Manual

SI30M-44M-60H-80H-IA-en-30

17

5.3 Multifunction Relay

Using two multifunction relays, each Sunny Island can control various functions and can display operating states and

warning messages. In battery backup systems, master multifunction relays are set permanently to control the contactors

within the automatic transfer switch.

Possible function or

output

Explanation

Controlling generators

The multifunction relay activates if a generator request is received from the Sunny Island

inverter's generator management. With the multifunction relay, you can control generators

equipped with electrical remote-start function or connect a signal generator for generators

with no autostart function (see Section 7.4.10 and 7.4.11).

Control of the tie switch

and of the contactors for

grounding

In battery backup systems, the multifunction relays control the contactors for grid coupling

and grounding.

Control of load-shedding

contactors

The multifunction relay is activated depending on the state of charge of the battery.

Depending on the configuration, you can install a one-level load shedding with one

multifunction relay or a two-level load shedding with two multifunction relays. You can also

adjust the thresholds for the state of charge of the battery depending on the time of day

(see Section 7.4.12).

Time control for external

processes

The multifunction relays can be time-controlled (see Section 7.4.13).

Display of operating

states and warning

messages

Each multifunction relay can display either one event or one warning message

(see Section 7.4.14).

Control of a battery-room

fan

The multifunction relay is activated when the charging current leads to the battery emitting

gasses. A connected battery room fan is switched on for at least one hour (see Section

7.4.15).

Control of an electrolyte

pump

Depending on the nominal energy throughput, the multifunction relay is activated at least

once a day (see Section 7.4.16).

Use of excess energy

In off-grid systems during the constant voltage phase, a multifunction relay is activated and

thus controls additional loads that can put any excess energy to good use (see Section

7.4.17).