8  Commissioning

SMA Solar Technology AG

64

SI30M-44M-60H-80H-IA-en-30

Installation Manual

8.1.2 Performing Basic Configuration of the Sunny Island

Requirement:

☐ The Sunny Remote Control must be connected to the master.
☐ All Sunny Island inverters must be switched on but not in operation (for how to switch on the Sunny Island inverter,

see the Sunny Island inverter operating manual).

☐ The Quick Configuration Guide (QCG) is started.

Procedure:

1. Turn the button on the Sunny Remote Control to the right and

select New System.

2. Press the button.
3. Turn the button to the right until Y flashes and press the button. This confirms your selection of New System.
4. Set the parameters of the QCG (carry out basic configuration in accordance with the installed system, see quick

reference guide of the installed system).

8.1.3 Setting Sunny Island Charger for Charge Controller/

Sunny Island Charger in Off-Grid Systems

Requirement:

☐ For systems with a maximum of four Sunny Island Charger devices, all Sunny Island Charger devices must be

connected to the master via a communication bus.

Procedure:

1. Switch to expert mode on the Sunny Remote Control (see Sunny Island operating manual).
2. Select the parameter 250.28 ChrgCtlOp and adjust as follows:

8.1.4 Commissioning the Battery Current Sensor in Off-Grid Systems

To operate the battery current sensor, you must set the type of the battery current sensor and start the

adjustments of the battery current sensor.
The Sunny Island distinguishes between battery current sensors of the types 50 mV and 60 mV. The types reflect the

amplification factor of the battery current sensor. The amplification factors are given in amperes per 50 mV or in

amperes per 60 mV, e.g. 400 A/60 mV.

Value

Explanation

Auto

System with AC sources (e.g. PV inverter)
The Sunny Island Charger or charge controller can also be present in the system.

SMA

System with Sunny Island Charger and without AC sources
A maximum of four Sunny Island Charger devices is installed.

NoFrq

System with charge controllers and without AC sources
The charge controllers are not Sunny Island Charger devices or the number is greater than

four Sunny Island Chargers.