7  Electrical Connection

Installation Manual

SI30M-44M-60H-80H-IA-en-30

49

7.4.18 Connecting the Signal Cable of the External Generator Request

An external control signal can transmit a generator request to the generator management. If you have

configured the generator management for the external generator request, the generator management starts

the generator if there is a high level present. The generator management stops the generator if there is a low level. As a

result, all generator run-times are complied with.

Figure 18: Connection of the control cable of an external generator request (example).

Requirements:

☐ The technical requirements of the digital input must be complied with (see Section 10 "Technical Data", page 94).

Cable requirements:

☐ Copper wire
☐ Conductor cross-section: 0.2 mm² to 2.5 mm²

Procedure:

1. On the Sunny Island, connect one insulated conductor of the control cable to terminal BatVtgOut+

(see Section 7.5.6 "Connecting BatVtgOut, DigIn, BatTMP, and BatCur", page 56).

2. Connect one insulated conductor of the control cable to terminal DigIn +.
3. Connect terminal BatVtgOut– to terminal DigIn –. Use the same conductor as in the control cable.