8  Commissioning

SMA Solar Technology AG

68

SI30M-44M-60H-80H-IA-en-30

Installation Manual

5. Set the parameters for equalization charge.

• Select the parameter 222.04 AptTmEqu and set it to the equalization charge absorption time recommended

by the battery manufacturer.

• Select the parameter 222.06 CycTmEqu and set it to the equalization charge cycle time recommended by the

battery manufacturer.

• Select the parameter 222.09 ChrgVtgEqu and set it to the cell-voltage setpoint recommended by the battery

manufacturer for equalization charge.

8.2.3 Changing the Battery Usage Through Battery Backup Systems

Without Increased Self-Consumption

Figure 20: State of charge ranges of the battery according to the time of year (example)

Adjusting the default values
The parameters for battery usage are set automatically to reasonable values during basic configuration for the

respective system. The parameter values can be adjusted if there are special requirements for the system or the

battery.

Range

Parameter and explanation of the range

Behavior of the Sunny Island inverter

BuRes

262.03 BUResSOC
Range for the battery backup system function

The Sunny Island uses this range for supplying the

battery backup grid when the utility grid fails. When

the utility grid is available again, the battery is

charged by the Sunny Island with nominal power

from the utility grid.