7  Electrical Connection

SMA Solar Technology AG

56

SI30M-44M-60H-80H-IA-en-30

Installation Manual

5. Connect the insulated conductors to the Relay1 or Relay2 terminals using the 3-pole terminal

(torque: 0.5 Nm to 0.6 Nm):

7.5.6 Connecting BatVtgOut, DigIn, BatTMP, and BatCur

Always connect the cables to connections BatVtgOut, DigIn, BatTMP, and BatCur as follows.

Additionally required material (not included in the scope of delivery):

☐ Suitable bootlace ferrules if using stranded wire

Cable requirements:

☐ Copper wire
☐ Conductor cross-section: 0.2 mm² to 2.5 mm²

Procedure:

1. Break through a suitable location in the cable feed-through plate with a sharp object.
2. Strip the cable insulation.
3. For stranded wires: press the bootlace ferrules onto the insulated conductors.
4. Lead the conductors through the hole in the cable feed-through plate into the Sunny Island.
5. Connect the insulated conductors to the 4-pole terminal (torque: 0.5 Nm to 0.6 Nm).

4.

:$51,1*

Danger to life from electric shock due to incorrect insulation
High voltage can be present in the control cable. Faulty insulation can result in a conductive connection with other

cables or components. Live components can be touched due to this connection. Touching can result in death or

serious injury due to electric shock.

• Cut the silicon tube to the length of the cable in the Sunny Island.
• Pull the silicone tube over the cable.

☑ The cable is double-insulated.

• Lead the cable into the Sunny Island making sure that it does not touch any data cables.

Connection

Explanation

NC

Closed when idle

C

Change-over contact

NO

Open when idle