7  Electrical Connection

SMA Solar Technology AG

38

SI30M-44M-60H-80H-IA-en-30

Installation Manual

Plug assignment:

Figure 12: RJ45 plug assignment

Figure 13: Design of the SI-COMSMA.BGx

Cable requirements:

☐ Classification: CAT5e
☐ Maximum cable length: 1,200 m

Procedure:

1. If an SI-COMSMA.BGx is not installed in the Sunny Island, install an SI-COMSMA.BGx in the Sunny Island

(see SI-COMSMA-NR mounting instructions):

• In single systems, install an SI-COMSMA.BGx in the Sunny Island.
• In a single-cluster system, install an SI-COMSMA.BGx in the master.
• In a multicluster system, install an SI-COMSMA.BGx in each master.

2. Connect the white data cable with open wires to the communication device (see installation manual of the

communication device).

Contact pin

Signal

Color coding of the insulated conductors

2

GND

Orange with white stripes

3

Data+ (A)

White with green stripes

6

Data − (B)

Green with white stripes

Position

Designation

A

Mounting hole

B

Type label

C

ComSmaIn pin connector

D

ComSmaOut pin connector