8  Commissioning

Installation Manual

SI30M-44M-60H-80H-IA-en-30

71

The following ranges result from the parameter default values:

Range

Parameter and explanation of the range

Behavior of the Sunny Island inverter

SlfCsmp

262.05 MinSlfCsmpSOC
Range for increased self-consumption
The value of 262.05 MinSlfCsmpSOC applies to

the shortest day of the year with seasonal adjustment

(see Section 8.2.4.1, page 69). If seasonal

adjustment is deactivated, only the value of

parameter 262.05 MinSlfCsmpSOC is used and

the BatRes range is increased accordingly.

The Sunny Island uses the battery for increased

self-consumption.

PVRes

262.04 PVResSOC
Range for maintaining the state of charge of the

battery
The range size is consistent year-round.

Excess PV energy is used for conserving the battery

charge. If no excess PV energy is available, the

Sunny Island switches to energy saving mode.

When the state of charge reaches the BatRes range

limit, the Sunny Island charges the battery up to half

of the PVRes range from the utility grid. To do so, the

Sunny Island charges the battery with maximum

efficiency at 25% of the nominal power of the

Sunny Island inverter.

BatRes

262.02 BatResSOC
Range for protection against deep discharge
This range can only be reached when the utility grid

fails. The value of parameter 262.02 BatResSOC

applies to the longest day of the year with seasonal

adjustment (see Section 8.2.4.1, page 69). If

seasonal adjustment is deactivated, the BatRes

range is increased accordingly.

If a utility grid is available, the Sunny Island charges

the battery using nominal power from the utility grid.

ProtRes

262.02 ProtResSOC
Range for protection during deep discharge
This range can only be reached when the utility grid

fails.

When this range is reached, the Sunny Island

switches off in order to protect the battery. When the

utility grid is available again, the system must be

charged manually ("Charging the Battery after Auto

Power Off", see Sunny Island operating manual).

Range

Lead-acid battery

Lithium-ion battery

Shortest day*

* December 21 (northern hemisphere) or June 21 (southern hemisphere)

Longest day**

** June 21 (northern hemisphere) or December 21 (southern hemisphere)

Shortest day*

Longest day**

MinSlfCsmp

65% to 100%

45% to 100%

30% to 100%

10% to 100%

PVRes

60% to 65%

40% to 45%

25% to 30%

5% to 10%

BatRes

10% to 60%

10% to 40%

3% to 25%

3% to 5%

ProtRes

0% to 10%

0% to 10%

0% to 3%

0% to 3%