beautypg.com

SMA SI 3.0-11 Installation User Manual

Page 28

background image

7  Electrical Connection

SMA Solar Technology AG

28

SI30M-44M-60H-80H-IA-en-30

Installation Manual

7.4.2 Connecting the Utility Grid in the System for Increased

Self-Consumption

Requirements:

☐ The system is not a battery backup system
☐ For connection of the Sunny Island inverter to the utility grid, there must be a circuit breaker and a type A

residual-current device on the distribution board (for circuitry overview, see the Quick Reference Guide

"SMA Flexible Storage System").

Procedure:

1. On the Sunny Island, connect the power cable to the terminals

AC2 Gen/Grid: Ensure that the cable is correctly connected (see

Section 7.5.2 "Connecting the AC Power Cable", page 52).

• Connect the line conductor to AC2 Gen/Grid L.
• Connect the neutral conductor to AC2 Gen/Grid N

TT

.

• Connect the grounding conductor to AC2 Gen/Grid PE.

2. Connect an additional grounding conductor to the AC1 Loads/SunnyBoys PE terminal if the power cable

conductor cross-section is smaller than 10 mm² (see Section 7.5.3 "Connecting the Grounding Conductor",

page 53).

4.

/05*$&

Damage to Sunny Island inverter due to reverse polarity or incorrect terminal lug selection
If the DC cables are swapped, high currents will flow after the load-break switch has closed and these can damage

the Sunny Island.

• Fasten the DC power cables to the DC connection with

M8x20 screws, ensuring correct polarity (torque: 12 Nm). In

doing so, ensure that the cable is connected correctly (see

Section 7.5.1 "Connecting the DC Power Cable", page 50)

and adhere to the following screw assembly: screw head |

spring washer | fender washer | terminal lug | DC

connection.

☑ The contact surfaces of the fender washers have full

contact with the terminal lugs.

This manual is related to the following products: