10 Technical Data
SMA Solar Technology AG
94
SI30M-44M-60H-80H-IA-en-30
Installation Manual
10 Technical Data
10.1 AC1 Connection for Stand-Alone Grid
Sunny Island
3.0M
Sunny Island
4.4M
Sunny Island
6.0H
Sunny Island
8.0H
Rated power
2,300 W
3,300 W
4,600 W
6,000 W
Power for 30 minutes at 25°C
3,000 W
4,400 W
6,000 W
8,000 W
Power for 5 minutes at 25°C
3,500 W
4,600 W
6,800 W
9,100 W
Power for 1 minute at 25°C
4,200 W
4,800 W
7,500 W
9,600 W
Maximum AC power for 3 s at 25°C
5,500 W
5,500 W
11,000 W
11,000 W
Maximum connectable power of the PV
inverters in off-grid systems
4,600 W
4,600 W
9,200 W
12,000 W
Rated grid voltage
230 V
230 V
230 V
230 V
Voltage range
202 V to 253 V
202 V to 253 V
202 V to 253 V
202 V to 253 V
Rated frequency
50 Hz
50 Hz
50 Hz
50 Hz
Frequency range
45 Hz to 65 Hz
45 Hz to 65 Hz
45 Hz to 65 Hz
45 Hz to 65 Hz
Frequency range of the set range
±5 Hz
±5 Hz
±5 Hz
±5 Hz
Rated current
10 A
14.5 A
20.0 A
26.1 A
Maximum output current as a peak
value for 60 milliseconds
60 A
60 A
120 A
120 A
Total harmonic distortion of the output
voltage (THD)
˂ 4.5%
˂ 4.5%
˂ 4%
˂ 4%
Displacement power factor cos φ
− 1 to +1
− 1 to +1
− 1 to +1
− 1 to +1
Recommended conductor cross-section
10 mm²
10 mm²
10 mm²
10 mm²
Maximum connectable conductor
cross-section
16 mm²
16 mm²
16 mm²
16 mm²
Cable diameter
9 mm to 18 mm
9 mm to 18 mm
9 mm to 18 mm
9 mm to 18 mm
Connection
Lever terminal
Lever terminal
Lever terminal
Lever terminal
Circuit breakers than can be tripped
Trip characteristic
B6
Trip characteristic
B6
Trip characteristic
B16 and C6
Trip characteristic
B16 and C6
Short-circuit rating
23.9 kW
23.9 kW
47.8 kW
47.8 kW