beautypg.com

SMA SI 3.0-11 Installation User Manual

Page 75

background image

SMA Solar Technology AG

8  Commissioning

Installation Manual

SI30M-44M-60H-80H-IA-en-30

75

Procedure:

1. Switch to expert mode on the Sunny Remote Control (see the Sunny Island inverter operating manual).
2. Set the following parameters for increased self-consumption:

✖ A parameter cannot be adjusted?

All ranges combined result in a value greater than 100%.

• Ensure that all ranges have been set correctly.

8.2.5 Changing the Battery Protection Mode in Off-Grid Systems

Function of the battery protection mode:
Battery protection mode protects the battery.
If the state of charge of the battery falls below a defined threshold, battery protection mode is activated. In battery

protection mode, the Sunny Island switches to standby mode or switches itself off. The battery protection mode has three

levels. One SOC threshold can be set for each level. Levels 1 and 2 of the battery protection mode have specific start

and end times and are therefore dependent on the time of day (see Section 9.3 "Setting Time-Dependent Functions",

page 92).

• Level 1

If the SOC drops below the threshold for level 1, the Sunny Island switches to standby between the start time and

end time. This way you can specify preferred times for the Sunny Island to be switched off if an energy deficit occurs.

• Level 2

If the SOC drops below the threshold for level 2, the Sunny Island switches to standby. Use the start time and end

time to define the time window in which no energy is anticipated from AC sources. Outside this time window, the

Sunny Island starts up every two hours to charge the battery. If no energy is available to charge the battery, the

Sunny Island remains on standby.
This means that, for example, in stand-alone grids with PV inverters, you can specify that the Sunny Island does not

start up at night, preventing it from consuming energy from the battery.

Parameter

Value

261.01 SlfCsmpIncEna

Enable

262.01 ProtResSOC

Range for protection during deep discharge as a percentage of the battery

capacity

262.02 BatResSOC

Range for protection against deep discharge as a percentage of the battery

capacity

262.03 BUResSOC

Range for the battery backup system function on the longest day of the year as a

percentage of the battery capacity
The range remains consistent year-round when seasonal adjustment is deactivated.

262.04 PVResSOC

Range for maintaining the state of charge as a percentage of the nominal capacity

262.05 MinSlfCsmpSOC

Range for increased self-consumption on the shortest day of the year as a

percentage of the battery capacity
When seasonal adjustment is deactivated, this value is used year-round for

increased self-consumption.

261.02 SlfCsmpPosSel

North for northern hemisphere or South for southern hemisphere

261.03 Saisonenable

No for no seasonal adjustment or Yes for seasonal adjustment

Battery protection mode for lithium-ion batteries cannot be changed
You can only change the battery protection mode if you are using lead-acid batteries. When using lithium-ion

batteries, the battery protection mode cannot be changed.