7  Electrical Connection

SMA Solar Technology AG

42

SI30M-44M-60H-80H-IA-en-30

Installation Manual

7.4.11 Connecting a Signal Generator for Generators Without Autostart

Function

Generators without an autostart function do not have electric starting devices. If you install a generator without

an autostart function, you can connect a signal generator (e.g. signal lamp) to the multifunction relay of the Sunny Island

inverter. As a result, the Sunny Island can signal when the generator is to be manually started and stopped.

Figure 16: Connecting a signal generator to signal a generator request (example)

Requirements:

☐ The technical requirements of the multifunction relay must be met (see Section 10 "Technical Data", page 94).

Cable requirements:

☐ Copper wire
☐ Conductor cross-section: 0.2 mm² to 2.5 mm²

Procedure:

2. Go to Section 8.1.5, page 66 and enter AutoGn in the table for configuration.

Connecting a signal generator in a cluster
Slaves control the generator less reliably than masters do.

• Connect the generator control preferably to the master.
• In a multicluster system, always connect the signal generator to the master of the main cluster.

1.

:$51,1*

Danger to life from electric shock due to incorrect insulation

• Connect the control cable on the Sunny Island to either

multifunction relay Relay1 or Relay2 (see Section 7.5.5

"Connecting Relay 1 and Relay 2", page 55). Use the C and

NO terminals.