Functionality in the PROFIBUS DPV2 device

76

B. Non-cyclic operation
If the desired total measuring range is not equal to the specified

single turn resolution * 2X (where x<= 12) the encoder operates

in non-cyclic operation. The non-cyclic operation is affected by the

parameter G1_XIST 1 Preset control as described below.

G1_XIST1 Preset control=Enabled
If the position value increases or decreases outside the maximum

value or below 0 with the parameter G1_XIST 1 Preset control

enabled, the device outputs the maximum position value within

the scaled total range for both position values G1_XIST 1 and

G1_XIST 2.

Example of non-cyclic scaling with G1_XIST 1 Preset control
enabled:

Total measuring range= Measuring units per revolution x number

of revolutions

Measuring units per revolution = 100

Number of revolutions= 50

(=50 is not equal to 2X where x<=12 means that a non cyclic

scaling will be used)

Total measuring range = 100 x 50 = 5000

Figure 23

Non-cyclic scaling G1_XIST 1 Preset control enabled