PROFIBUS IO data description

40

5.4.2 Standard telegram 82

Standard telegram 82 uses 4 bytes for output data from the

master to the encoder gateway and 14 bytes of input data from

the encoder gateway to the master.

Output data from the master:
2 bytes Control word 2 (STW2_ENC)

2 bytes Control word (G1_STW)

IO Data (word)

1

2

Set point

STW2_ENC

G1_STW

Input data to the master:
2 bytes Status word 2 (ZSW2_ENC)

2 bytes Status word (G1_ZSW)

4 bytes Position value 1 (G1_XIST1)

4 bytes Position value 2 (G1_XIST2)

2 bytes Velocity value A (NIST_A)

IO Data (word)

1

2

3

4

5

6

7

Actual value

ZSW2_ENC G1_ZSW G1_XIST1

G1_XIST2

NIST_A

Note: Telegram 82 is only supported by the encoder gateway.

It is not supported by the absolute encoder.