Encoder gateway installation

17

The cable gland gateway shall be equipped with twisted pair

shielded cable in accordance with EN 50170 and PROFIBUS

guidelines. The guidelines recommend a conductor area higher

than 0,34 mm

2

. Permissible outer cable diameter is ø 8 mm to ø

10 mm for the bus lines cables. Located inside the back cover are

four screw terminals containing the required bus line terminals

marked A and B. Cable glands not used, should be replaced with

a M16 filler plug to ensure proper sealing.


Note: Tighten all screws in the terminal, even if no cable has

been attached.


Note: The two A terminals are internally connected to each

other and the two B terminals are also connected to
each other so it does not matter to which the bus lines
are connected to.