Functionality in the PROFIBUS DPV2 device

72

The steps below should be followed from the master when

modifying the Preset value parameters:

• Read the requested Preset value parameter and check if the

returned value meets the application requirements. If not,

proceed with the following steps.

• Write the Preset value into the individual parameter.

• Store the value in the non volatile memory by PROFIdrive

parameter 971 if the value should be valid also after the next

power on sequence.

Parameter

Meaning

Data type

Preset value

The preset value for encoders with a

measuring range of maximum 32 bits

Integer32

Preset value 64

The preset value for encoders with a

measuring range exceeding 32 bits

Integer64

Table 38

Preset value parameters

Note: The preset function should only be used at encode

standstill

Note: The number of possible preset cycles is unlimited.

Note: If scaling is used the preset function shall be used after

the scaling function to ensure that the preset value is
entered in the current measuring unit.

Note: There is no preset activated when the preset value is

written to the encoder. The preset function is controlled
by bits in the control and status words (G1_STW and
G1_ZSW) and bit in the operating parameters. The
preset value is used when a preset is requested by bit
12 in the Control word (G1_STW).