PROFIBUS IO data description

46

5.8 Status word 2 (ZSW2_ENC)

The status word 2 (ZSW2_ENC) is referred to as the slave’s sign

of life and it includes the fault buffer handling and Control by PLC

mechanism from PROFIdrive ZSW1 and the Slave Sign-Of-Life

mechanism from PROFIdrive ZSW2. This signal is mandatory for

controlling the clock synchronization.

Bit

Function

0...2

Reserved

3

Fault present/No fault

4,8

Reserved

9

Control requested

10,11

Reserved

12...15

Encoder sign-of-life

Table 16

ZSW2_ENC definition

Bit

Value

Significance

Comments

3

1

Fault present

Unacknowledged faults or currently not

acknowledged faults are present. The

fault reaction is fault-specific and device-

specific. The acknowledging of a fault

may only be successful if the fault case

has disappeared or has been removed

before. If the fault has been removed the

encoder returns to operation. The related

fault numbers are in the fault buffer.

0

No fault

9

1

Control requested

The automation system is requested to

assume control.

0

No control requested

Control by automation system is not

possible, only possible at the device or

by another interface.

12-15

Encoder sign-of-life

Table 17

Detailed assignment of Status word 2 (ZSW2_ENC)