3 base mode parameter access, 1 general characteristics, 2 parameter requests and responses – HEIDENHAIN PROFIBUS-DP (DPV2) User Manual
Page 55: 3 changing the preset value, Base mode parameter access, General characteristics, Parameter requests and responses, Changing the preset value, Table 23, Write of preset value

Acyclic parameter data
55
7.3 Base mode parameter access
7.3.1 General characteristics
A single acyclic parameter can be transmitted in one access. A
parameter access can be up to 240 bytes long.
7.3.2 Parameter requests and responses
Request header: Request ID, DO-ID and number of parameters of
the access.
Parameter address: One address for each parameter, if several
parameters are accessed.
Parameter value: If the Request ID is 0x02 (change value) the
value is set in the request and if the Request ID is 0x01 (request
value), the value appears in the reply.
7.3.3 Changing the preset value
The table below shows the structure of a change value request.
Write of Preset value, parameter 65000 parameter request
Request reference
0x00
Request ID
0x02
0x02->Change value,
0x01->read value
DO-ID (axis)
0x01
Drive object ID
No of parameters
0x01
Attribute
0x10
0x10->value
No of elements
0x00
Parameter number
0xFDE8
Parameter 65000
Sub index
0x0000
Format
0x04
Data type integer 32
Number of values
0x01
Table 23
Write of preset value