Absolute encoder installation

25

The cable gland encoders shall be equipped with twisted pair

shielded cable in accordance with EN 50170 and PROFIBUS

guidelines. The guidelines recommend a conductor area higher

than 0,34 mm

2

. Permissible outer cable diameter is ø 8 mm to

ø 10 mm for the bus line cables. Located inside the back cover are

four screw terminals containing the required bus line terminals

marked (A) and (B).

Cable glands not used should be replaced

with a M16 filler plug to ensure proper sealing.

The (A) terminal shall be used to connect the A-line.

The (B) terminal shall be used to connect the B-line.

Figure 10

Terminal connections of bus line cables

Note: Tighten all screws in the terminal, even if no cable has

been attached.


Note: The two A terminals are internally connected to each

other and the two B terminals are also connected to
each other so it does not matter to which terminal the
bus lines are connected to.