Acyclic parameter data

57

7.4 Detailed description of supported parameters

7.4.1 Parameter 918, read only

918 unsigned int, presents the node address of the device.

7.4.2 Parameter 922, read only

922 unsigned int, presents which telegram is used. Telegram

81, 82, 83 or 84 is possible.

7.4.3 Parameter 925, read/write

925 unsigned int, maximum allowed MLS (Master sign-of-life)

error. Parameter 925 may be used to set a maximum on how

many consecutive Sign-of-life failures may occur.

7.4.4 Parameter 964, read only

964 unsigned int, Device indentification

964[0] = Manufacturer Id. This is set during manufacturing of the

encoder.

964[1] = 0 DU Drive unit type, always set to 0.

964[2] = 201 Software version

964[3] = 2009 Software year

964[4] = 2805 Software day and month

964[5] = 1 Number of drive objects (D

7.4.5 Parameter 965, read only

965 OctetString 2, Encoder profile number

965[0] =0x3D Encoder profile number

965[1] = 31 or 41 Encoder profile version, set by customer

(user_parameters)

7.4.6 Parameter 971, read/write

971 unsigned int, Store the local parameter set to a non volatile

memory. Preset value is saved when writing value 1 and is set to

0 by the encoder firmware when finished. This means that the

preset value has been saved when reading back value 0.

7.4.7 Parameter 974, read only

974 unsigned int

974[0] = 96 Max array length supported by parameter channel.

974[1] = 1 Numbers of multi parameters, 1 = no support of

multi parameters.

974[2] = 1000 max time to process parameter request,

n x 10 ms.