6 compatibility mode, Compatibility mode, Table 36 – HEIDENHAIN PROFIBUS-DP (DPV2) User Manual
Page 70: Compatibility mode attributes, Table 37, Compatibility mode definition

Functionality in the PROFIBUS DPV2 device
70
8.6 Compatibility mode
This parameter defines if the encoder should run in a mode
compatible to Version 3.1 of the Encoder Profile. See below for an
overview of functions affected when the compatibility mode is
enabled.
Attribute
Meaning
Value
Enable
Compatibility with encoder profile v3.1
0
Disable
No backward compatibility (default)
1
Table 36
Compatibility mode attributes
Function
Compatibility mode enabled
(=0)
Compatibility mode disabled
(=1)
Control by PLC
(STW2_ENC)
Ignored, the control word
(G1_STW) and setpoint values
are always valid. Control
requested (ZSW2_ENC) is not
supported and is set to 0.
Supported
User parameter
Maximum master
sign-of-life failures
Supported
Not supported, one sign-of-life
failure tolerated. PROFIdrive
P925 is optional to control the
life sign monitoring.
User parameter
Alarm channel
control
Supported
Not supported, the application
alarm channel is active and
controlled by a PROFIdrive
parameter
P965 Profile version 31 (v3.1)
41 (v4.1)
Table 37
Compatibility mode definition