beautypg.com

Grass Valley XtenDD DD User Manual

Page 64

background image

5. Connection and Statup

5 - 2

Planning and Installation - Rev. 3 / 04.2005

AC IN

Internal protective earth

Video earth

Case

(insulated mounting)

PE

TE

Internal wiring

For additional grounding of the devices, the following methods are possible:

1. As a potential compensation or as an additional earth conductor with large

cross section:

The jumper between the PE and TE terminal screws must be in place. The cen-

tral protective conductors of the studio have to be screwed to the PE terminal

screw. The protective conductor should have a cross section greater than that

of the neutral conductor N of the mains cable, however, 2.5 mm

2

at least (with

protected installation) (4mm

2

with unprotected installation). Fusing up to 25A.

Standards: VDE 0800, part 2, table 1/ VDE 0100 T.540 / IEC 364-5-54, 543.1.

Color code of the insulation: green/yellow.

2. Additional noiseless functional protective earth FPE (functional earth with pro-

tective qualities) low on extraneous voltage:

If required, e.g. in studios with separate protective and technical earth systems,

the jumper between the PE and TE terminals can be broken. In this case, the

central functional earth has to be additionally connected to the TE terminal

screw.

The cross section has to be dimensioned as described above. A low-imped-

ance interconnection of both earth conductors must be provided at the central

studio grounding point or at the earth bus.

Protective earth

Video earth

Central
earthing point

Device
Example 1

Device
Example 2

Jumper not broken!!

Jumper broken!!

TN-C power systems

In case of TN-C power systems (combination of neutral conductor and protective

conductor), it is necessary to observe the regulations in conformity with IEC

364-5-54 (VDE 0100 T-540) and IEC 364-4-41, IEC 364-4-47 (VDE 0100 T.410)

or the applicable national regulations.