14 keypad/dtmf access users, Keypad/dtmf access users, Figure 3.29 keypad/dtmf access users configuration – RLE FMS V.1.13 User Manual
Page 83: Table 3.18, Keypad/dtmf access users configuration options

rletech.com
FMS User Guide
83
3
Web Interface Configuration
3.4.14 Keypad/DTMF Access Users
If your FMS has a keypad attached to it, use the Keypad/DTMF Access Users link to
configure a maximum of 20 access codes and user names.
Figure 3.29
Keypad/DTMF Access Users Configuration
Option
Description
Id Code
Up to six digits long, users enter this code into the keypad to gain
access.
User Name
Enter a user name that will be linked to the access code. The user
name can be up to 20 characters long.
Type
Permanent - The code is active for an unlimited amount of time.
Temporary - This code is only active during the parameters
specified in the Temporary Time Settings.
Temporary Time
Setting
Access codes designated as temporary are only active during this
specific window of time, which is established near the bottom of the
Keypad Configuration Page.
Configure the appropriate span of time and click the Set Temporary
Time button to activate the settings. The amount of time remaining
in the temporary window displays on the countdown clock.
Once the time frame has expired, the temporary users will not be
allowed access. However, their information will remain in the
Keypad/DTMF field until it is manually removed. While temporary
users will not be allowed access to a facility after their allotted time
slot, no alarm notification will be transmitted if they try to re-enter
the facility through the keypad. Their information must be manually
removed from the system in order to activate the alarm notification.
Table 3.18
Keypad/DTMF Access Users Configuration Options