2 pue/dcie trending, Pue/dcie trending, Figure 3.47 data for third party applications – RLE FMS V.1.13 User Manual
Page 111: Format trends

rletech.com
FMS User Guide
111
3
Web Interface Configuration
9
Information has also populated at the bottom of the chart. Use this information if you wish
to output the PUE/DCiE information to a third party application or generate PUE/DCiE
trending information. Modbus, BACnet, and SNMP output information is provided.
Figure 3.47
Data for Third Party Applications
3.4.26.2 PUE/DCiE Trending
Now that the FMS is generating PUE/DCiE information, it can log long-term trending data.
The trending program can log 3840 entries. Once 3840 entries have been logged, the system
will eliminate 40 entries at a time and overwrite the data, from oldest to newest. Long-term
trending is the most effective way to use PUE/DCiE data.
Format Trends
1
On the FMS interface, go to Configuration>Trends.
2
You may already have some trending tasks operating on the FMS. Select the next available
index number. Use the following points to trend your data:
3
Select Modbus/SNMP as the type.
4
Now, determine the interval at which you wish to trend the data. The interval is selectable,
from a 1 minute interval to an 8 hour interval - it just depends how detailed you’d like your
data to be. At a 1 minute interval, the FMS will store approximately 2.5 days worth of data
Point Value
Trended Data
629
DCiE 1
630
PUE 1
631
DCiE 2
632
PUE 2
633
DCiE 1 + 2
634
PUE 1 + 2
635
Summary 1
636
Summary 2