RLE FMS V.1.13 User Manual
Page 150

150
FMS User Guide
970.484.6510
4
Advanced Communications - Modbus, BACnet, and Telnet
Object Type
Select the appropriate object type:
•
Analog Input
•
Analog Output
•
Analog Value
•
Binary Input
•
Binary Output
•
Binary Value
•
Multistate Value
Instance-PV
Designate the appropriate instance-pv.
Binary Alarm
Check this box if the register is a binary alarm.
Label
Enter a label to describe the Data Point.
UOM/Map Label
Specify the unit of measure you are using for this specific point.
Log Index
Applies to Data Types Signed Int, Unsigned Int, Long and Float.
The FMS has 232 entries reserved for logging (Min, Hour and Day
Logs). Enter a value of 1 to 232 if the point is to be internally logged
on the FMS. Each register to be logged requires a unique entry
number.
Enumerated Label
Set
Sets of enumerated labels can be configured from the Enumerated
Labels Configuration link on the bottom of the Modbus/Snmp/
Bacnet Slave units page. If you have a label set configured,
designate which one you’d like to use here.
Analog Alarm Type
Designate which type of analog alarm this will be.
Alarm Thresholds:
High 2, High1, Low1,
Low2
Set high and low - or major and minor - thresholds for alarm analog
alarm values being read by these points.
Multistate Active
Value
If you’d like to designate an multistate active value, do so here.
Snmp Trap
Recipients
The SNMP/Syslog page allows you to configure SNMP trap
recipients. Once those are configured, you can designate which IP
addresses should receive traps for this register.
Map Box Size
Customize the size of the mapped object. By default, the height of
the object, as it appears on the map, is approximately 20 pixels,
and the width automatically adjusts to the length of the text. This
setting allows users to expand the size of the object to fill a defined
area.
Map Coordinate
Fine tune the location of the object on the map. Refer to
(Facility Mapping)” on page 114
for further information.
Graphical Mapping
Designate the device’s location on the FMS graphical map. Refer to
“Map (Facility Mapping)” on page 114
for further information.
Test Map
View the mapped location of the point you’re currently configuring.
Option
Description
Table 4.8
Individual Bacnet Register Configuration Options