3
Web Interface Configuration
Low Limit1 (Minor)
Applies only to analog 4-20mA inputs.
The FMS will record an alarm and send notification when the FMS
calculated value falls below this limit. The Low Limit 1 and Low
Limit 2 are disabled when they are both set to 0.
Low Limit2 (Major)
Applies only to analog 4-20mA inputs.
The FMS will record an alarm and send notification when the FMS
calculated value falls below this limit. The Low Limit 1 and Low
Limit 2 are disabled when they are both set to 0. Low Limit 2 will
also activate any designated relays.
Pager Alarms
Use the Configuration>Modem/Phone Numbers/Pagers link to
configure alarm recipients. You can configure up to 15 phone
numbers, and each will go into a numbered slot, 1 - 15.
Then come back to this field and designate up to five recipients who
should be notified when this point goes into alarm. Separate the
recipients’ ID numbers with commas. The FMS will first dial the
lowest number listed, regardless of the order in which the numbers
are listed.
Enter zero to disable this feature.
Example: If the Alarm dial out string is set to “3, 5, 1, 0, 0,” the FMS
will dial Pager #1, Pager #3 and then Pager #5 when an alarm
occurs. Pager notification will be sent when an input alarms (high
limit 2, high limit 1, low limit 1, low limit 2 is exceeded or the digital
input is in alarm). See
3.4.13, “Modem/Phone Numbers/Pagers” on
for more information.
Label
Enter a unique name for this input.
Applies to all input types except “Not Configured.”
•
For Analog input types, this label is displayed on the FMS Main
Menu and the Input Configuration Menu. When the input
alarms and/or returns to normal, the label is included in the
Alarm History and notification messages.
•
For Digital NO and Digital NC inputs, the label is displayed on
the FMS Main Menu, Input Configuration Menu, Alarm History
page and in notification messages only when the device is in
alarm.
•
For Digital Status inputs, the label is displayed on the FMS
Main Menu when the input is on. When the input turns on, the
label is also included in the Digital Status History.
Option
Description
Table 3.3