Configuration, 1 inputs and relays, Inputs and relays – RLE FMS V.1.13 User Manual
Page 43: Figure 3.4

rletech.com
FMS User Guide
43
3
Web Interface Configuration
3.4. Configuration
The Configuration page allows authorized users with administrator or read-write privileges to
adjust the FMS settings. Each link on the Configuration page displays more information about
specific configuration settings.
Figure 3.4
Configuration Page
NOTE: If any of the fields within the sub-menus are edited, be sure to click the Submit
Changes button to save the changes. If you edit the fields and navigate from the web
pages without clicking the Submit Changes button, all changes will be lost.
3.4.1 Inputs and Relays
Inputs and Relays allows users to program specific parameters for each FMS input and relay.
Only installed inputs and relays are displayed.
Different FMS models allow different numbers of inputs and relays. A1U will include the
Main Board inputs, and has room for one expansion card - either an A card or a C card.
A 2U FMS allows 4 expansion cards to be added to the unit - each expansion card slot can be
outfitted with either an A card or a C card.
♦
Main Board Inputs 1-8 - Every FMS has a main board. This board provides 8 inputs
configurable as analog 4-20mA or digital NO/NC.
♦
Expansion Card A Inputs and Outputs- adds an additional 12 inputs, configurable as analog
4-20mA, 0-5V, 0-10V or digital NO (cannot be configured as NC), as well as 8 form C
relay outputs.
♦
Expansion Card C Inputs - adds an additional 24 digital NO/NC inputs. There are no
additional relay outputs on a C card