1 cb# links, Cb# links, Table 4.9 – RLE FMS V.1.13 User Manual
Page 154: Circuit breaker configurations for individual bcms

154
FMS User Guide
970.484.6510
4
Advanced Communications - Modbus, BACnet, and Telnet
4.6.1.1 CB# Links
Pressing a CB # (CH#) link displays the Circuit Breaker Configurations for each BCM.
Figure 4.18
Circuit Breaker Configurations for Individual BCMs
Option
Description
Label
Enter a label to describe the circuit breaker. The label is included in
notifications and for identification on the Slave Unit Monitoring
page.
Zero Amp Enable
Check to enable alarm and notification if the branch circuit current
falls below the zero amp level as set on the Slave Configuration
page.
Breaker Size
Enter the circuit breaker size in the BCM.
Warning Threshold
Enter the warning threshold level-in percent-in the BCM.
Alarm Threshold
Enter the alarm threshold level-in percent-in the BCM.
Warning Time Delay
Enter the warning time delay-in seconds-in the BCM.
Alarm Time Delay
Enter the alarm time delay-in seconds-in the BCM.
Table 4.9
Circuit Breaker Configurations for Individual BCMs