Web Interface Configuration
3.5. History
The History link provides access to a wide variety of logged historical data for the FMS.
3.5.1 Alarm History
Alarm History displays the last 256 alarms captured by the FMS. Alarms are ranked from
most recent (top of the list) to least recent (bottom of the list).
Figure 3.66
Alarm History Page
The following format is used to record each alarm entry:
Date Time AH###-ID-Condition Severity (Value UOM) Label
♦
Date and Time is the internal date and time stamp of the alarm condition.
♦
AH### is the alarm entry index.
♦
ID is the alarm identifier number; see
Appendix E, “Alarm ID Reference Tables” on
.
♦
Condition is On, High1, High2, Low1, Low2, or RTN (Returned to Normal).
♦
Severity is Critical, Major, Major*Hi, Minor, Minor*Hi, Warning, or Clear
♦
Label is the alarm descriptor, up to 64 characters long.
♦
Value and Unit of Measure (UOM) is captured for analog channels only. The value
recorded is the actual analog value that exceeded its alarm threshold.
The Alarm History log entries are color-coded as follows:
Color
Description
Red
A point configured for dial out (pager) is in alarm and is unacknowledged. The
alarm will be red if the point is configured for both pager and email notification.
Orange
A point not configured for dial out (pager) is in alarm and is unacknowledged.
Blue
The alarm has been acknowledged.
Black
The alarm has returned to normal.
Table 3.31
Alarm History Log Entries