3.4.6 Trends
This feature allows users to configure custom trending on an analog point, either physical or
Modbus.
Figure 3.15
Trends Configuration Page
Data can be trended for 8 or 32 points. If you choose to trend 8 points, the FMS will trend
16128 entries per point. If you choose to trend 32 points, the The FMS compiles 3840 entries
per point. Once the maximum number of entries has been reached, the FMS eliminates 40
entries at a time and overwrites the data, from oldest to newest. You determine the time
interval for the data collection, depending on how detailed you’d like the information.
Time intervals range from 1 minute to 8 hours, and total sample collection is as follows:
Figure 3.16
Trend Configuration Menu Options
Interval
Samples per
Day
Total Days
Interval
Samples per
Day
Total Days
1 minute
1440
2.6
2 hours
12
320
5 minutes
288
13.3
4 hours
6
640
15 minutes
96
40
6 hours
4
960
1 hour
24
160
8 hours
3
1280
Table 3.8
Trend Interval Chart
Option
Description
Point
The physical channel or Modbus index number.
Type
Select either Physical or Modbus SNMP.
Interval
Select the Interval you’d like to use for trending.
Info
Uneditable field.
Format
Once all your information has been filled out, click this button.