Technical Specifications
Expansion Cards
EXP-A-24 or EXP-A-48
1U accommodates 1 expansion card; 2U accommodates up
to 4 expansion cards
24V Falcon requires EXP-x-24 option cards; 48V Falcon
requires EXP-x-48 option cards
12 analog inputs (jumper selectable for 4-20mA, 0-5VDC or
0-10VDC) and digital inputs (non-isolated, individual ground
only);
8 Form C Relay Outputs, 1A @ 24VDC, 0.5A resistive @
120VAC
EXP-C-24 or EXP-C-48
24 Digital Inputs, 3000VAC RMS optically isolated (common
ground or individual ground)
Communications Ports
Ethernet
10/100BaseT, RJ45 connector; 500VAC RMS isolation
EIA-232
DB9 female connector; 9600 baud; 3000VAC RMS optically
isolated; 15kV ESD protection
EIA-485 (selectable as EIA-232)
Two-wire half duplex; terminal block (selecting EIA-232
switches to DB9 male connector); 1200, 2400, or 9600 baud
configurable; 3000VAC RMS optically isolated
Modem (RJ11 Telco) – Optional
V.34bis/33.6 kbps; DTMF capable; PPP-Enabled; FCC Part
68 approved; 1500VAC RMS isolation barrier; 2100V peak
surge protection
Protocols
TCP/IP, UDP/IP, ICMP/IP, FTP,
NTP
IPv4
HTTP/HTML, SNPP, Telnet
1.1/4.0; up to 10 URL links to other IP addressable
cameras/devices; webpages comply with Rehabilitation Act
of 1973, sections 504 and 508, US Dept of Education
(website accessibility for computer users with disabilities)
SNMP
V1: MIB-2 compliant; NMS Manageable with Get, Set, and
Traps; V2c: Traps or Informs; V3 (optional)
SMTP (Email)
Supports Client Authentication (plain and login); compatible
with ESMTP Servers
Modbus
RTU transmission protocol; function codes: Slave - 03;
Master - 01,02,03,04
Modus/IP
Modbus Slave; TCP/IP transmission protocol
BACnet/IP
Reads up to 106 instances and converts to SNMP and
Modbus
Terminal Emulation
VT100 compatible
TAP (Pager)
Telocator Alphanumeric Protocol Ver1.8
Table J.1