Appendix a - save, load, copy setpoints, Copying & restoring previously saved setpoints – Orion System VCM-X/RNE Controller User Manual
Page 81
VCM-X / RNE Operator Interface SD
APPENDIX A - SAVE, LOAD, COPY SETPOINTS
81
Copy Setpoints - Network Mode
To copy a saved setpoints fi le to other controllers on the network do
the following:
From the Save Setpoints Screen shown below:
Save Setpoints
Press Enter To Save
Press
<
>
once to access the Copy Setpoints Screen shown below.
Copy Setpoints
From Loop 1
From Unit 2
Press Enter to Copy
In the ‘From Loop’ fi eld, enter the Loop of the controller you want to
copy the setpoints from. In this example it is ‘1’. Then press
.
In the ‘From Unit’ fi eld, enter the Unit ID of the controller you want to
copy the setpoints from. In this example it is ‘2’. Then press
.
Now your cursor will be on the last line, and you can press
once more to copy the setpoint fi le from unit 102 to unit 103.
You will receive a confi rmation that the copy was successful.
Save & Copy Setpoints - Stand-Alone
Mode
The instructions for Stand-Alone Mode are exactly the same as Network
Mode, except that there is no need to enter a Loop number in the Unit
ID number fi eld and in the Copy Setpoints Screen, enter a zero in the
‘From Loop’ fi eld.
Restore Setpoints - Network or
Stand-Alone Mode
The Restore Setpoints feature is used to reload a saved setpoints fi le
from one controller back to itself. This could be useful if setpoints or
confi gurations were changed and need to be reset.
You can perform this function on a networked system; however, the
Modular Service Tool needs to be directly connected to the controller
you wish to restore previously saved setpoints to.
From the Save Setpoints Screen shown below:
Save Setpoints
Press Enter To Save
Press
<
>
four times to access the Restore Setpoints Screen shown
below.
Restore Setpoints
Press Enter to Load
Press
. This will reload the setpoints from the saved fi le. You
will receive confi rmation that the setpoints were loaded successfully.
Copying & Restoring Previously Saved Setpoints