Vcm-x / rne status, Vcm-x / rne status screens, Vcm-x / rne operator interface sd 63 – Orion System VCM-X/RNE Controller User Manual
Page 63

VCM-X / RNE STATUS
VCM-X / RNE Operator Interface SD
63
VCM-X / RNE Status Screens
Line 2-3 Current Head Pressure Cooling or Reheat Setpoint
If you are using the VCM-X E-BUS Modular, VCM-X
E-BUS WSHP, or RNE Controller and have a One
Condenser or Two Condenser Head Pressure Module
attached to the unit, the Head Pressure Cooling or Reheat
Setpoint will display, depending on what mode the Module
is in. This status value will show 0 if not in the Cooling or
Dehumidifi cation Mode.
Status Screens 24 & 25 - Head Pressure
Condenser Fan #1 & #2
VCMX-M/RNE Cnfg ID 102
Cond. Fan Sect. #1
Head Pr.....: 0PSI
Cond Fan Spd: 0%
VCMX-M/RNE Cnfg ID 102
Cond. Fan Sect. #2
Head Pr.....: 0PSI
Cond Fan Spd: 0%
Line 2 Condenser Fan #1 or #2
If you are using the VCM-X E-BUS, VCM-X WSHP or
RNE Controller and have a One Condenser or Two
Condenser Head Pressure Module attached to the unit, this
line displays Condenser Fan #1 or #2.
Line 3 Head Pressure
This line indicates the highest of up to 4 current Head
Pressure readings on a One Condenser Head Pressure
Module. If using a Two Condenser Head Pressure Module,
this line indicates the highest of the fi rst 2 current Head
Pressure readings on that module.
Line 4 Condenser Fan Speed
This line displays the speed of the associated Condenser
Fan (0-100%) that is currently necessary to maintain the
Head
Pressure
Setpoint.
Status Screen 26 & 27 - Head Pressure
Condenser Fan #3 & #4
VCMX-M/RNE Cnfg ID 102
Cond. Fan Sect. #3
Head Pr.....: 0PSI
Cond Fan Spd: 0%
VCMX-M/RNE Cnfg ID 102
Cond. Fan Sect. #4
Head Pr.....: 0PSI
Cond Fan Spd: 0%
Line 2 Condenser Fan #3 or #4
If you are using the VCM-X E-BUS, VCM-X WSHP or
RNE Controller and have a second Two Condenser Head
Pressure Module attached to the unit, this line displays
Condenser Fan #3 or #4.
Line 3 Head Pressure
This line indicates the highest of the second two Head
Pressure readings of the Two Condenser Head Pressure
Module.
Line 4 Condenser Fan Speed
This line displays the speed of the associated Condenser
Fan (0-100%) that is currently necessary to maintain the
Head
Pressure
Setpoint.
Status Screen 22 / RNE - Full Digital Signal
RNE Cnfg ID 102
Full Digital
Stage 1 Sig: 0%
Stage 2 Sig: 0%
Line 2 Full Digital Signal
If using a Full Digital Module ( OE370-23-FD-A) or
Water Source Heat Pump Module (OE334-23-WPM-A)
this screen will appear.
Line 3 Stage 1 Signal Percentage
This is the modulating signal percentage for Compressor
1 if there are two Compressors, or for the fi rst two
Compressors if there are four Compressors.
Line 4 Stage 2 Signal Percentage
This is the modulating signal percentage for Compressor
2 if there are two Compressors, or for the last two
Compressors if there are four Compressors.
Status Screen 23 - Head Pressure Setpoint
VCMX-M/RNE Cnfg ID 102
Current
Head Pr Sp: 0 PSI