Vcm-x configuration, Vcm-x confi guration screens – Orion System VCM-X/RNE Controller User Manual
Page 32
Zone
Zone
VCM-X CONFIGURATION
VCM-X / RNE Operator Interface SD
32
Confi guration Screen #47 - Broadcast Internal
Time Clock
VCM-X Cnfg ID 59
Broadcast Internal
Time Clock: NO
Use < Or > To Change
This broadcast sends the time from the VCM-X’s Internal Time Clock
to all controllers on its local loop. This broadcast needs to be confi gured
on a VAV or Zoning System using the VCM-X with Orion VAV/Zone
controllers. A network communications device is required in order for
this feature to operate, but can also be used to synchronize all control-
lers on the local loop. Select YES to Broadcast Internal Time Clock.
Default is NO.
Confi guration Screen #48 - Broadcast Internal
Schedule
VCM-X Cnfg ID 59
Broadcast Internal
Schedule: NO
Use < Or > To Change
This is always required when you have VAV/Zone controllers connected
to this VCM-X Controller. This will broadcast the Occupied and Unoccu-
pied Condition of the VCM-X Controller to all VAV/Zone controllers on
the local loop. Select YES to Broadcast Internal Schedule. Default is NO.
Confi guration Screen #49 - Broadcast VAV
Boxes Force to Max
VCM-X Cnfg ID 59
Broadcast VAV Boxes
Force To Max: NO
Use < Or > To Change
This broadcast is to ensure the VAV/Zone Controllers will drive their
dampers to the Max Airfl ow Damper Position during Morning Warm-
up. This is important to allow the proper amount of airfl ow for Heating
in the HVAC unit. Select YES to Broadcast VAV Boxes Force to Max.
Default is NO.
Confi guration Screen #50 - Broadcast VAV
Boxes Force to Fixed
VCM-X Cnfg ID 59
Broadcast VAV Boxes
Force To Fixed: NO
Use < Or > To Change
Select YES to have all VAV/Zone controllers connected to this VCM-X
Controller forced to their “Fixed Airfl ow” Position during the Morning
Warm-up Mode of operation. See the VAV/Zone Controller Setpoint
Screens for setting of the “Fixed Airfl ow” position. Default is NO.
Confi guration Screen #51 - 1 HVAC Unit with
Boxes on Multiple Loops
VCM-X Cnfg ID 59
1 HVAC Unit w/ Boxes
On Multi. Loops: NO
Use < Or > To Change
Select YES to have all broadcasts that have been confi gured on Confi gu-
ration Screens 43 through 48 sent to all local loops on the entire system,
not just the local loop the VCM-X Controller is on. This is normally
only required if you have a large HVAC unit that requires more than
the 58 VAV/Zone Controllers normally allowed on the local loop. This
allows other VAV/Zone Controllers connected on additional local loops
to receive the required broadcasts. This only is allowed when you have
a single VCM-X Controller with VAV/Zone Controllers on multiple
loops. Other VCM-X or add-on devices may be connected but no other
VCM-X with VAV/Zone Controllers can be connected on the system.
Default is NO.
Confi guration Screen #52 - Uses R410A
Refrigerant
VCM-X Cnfg ID 59
Unit Uses R410A
Refrigerant: NO
Use < Or > To Change
Select YES if your HVAC unit uses R410A Refrigerant. Default is NO.
Confi guration Screen #53 - Main Fan
Maximum Voltage
VCM-X Cnfg ID 59
Max Main Fan Aout
Voltage: 10.0 VDC
[ 0 VDC - 10 VDC ]
Enter a value between 0.0 and 10.0 VDC for the main fan’s maximum
output voltage. The Static Pressure and Output % Status Screen will
display 0% to 100%, but the output will range from 0 VDC to the value
set in this screen. Default is 10.0 VDC.
This screen will appear if using a VCM-X E-BUS Controller.
VCM-X Confi guration Screens