VCM-X / RNE Operator Interface SD

VCM-X / RNE SETPOINTS

53

Description

Minimum

Default

Maximum

Heat Pump

Auxiliary Heating Delay

0 Min

3 Min

30 Min

Setpoint Screen #34 - Heat Pump Defrost

Setpoints

VCM-X / RNE Spts

Heat Pump Defrost

Defrost Tmp: 30ºF
Defrost Tmr: 30 Min

The Defrost Temp Setpoint is the Coil Suction Temperature at which
the unit will go into Defrost Mode during Heat Pump Heating opera-
tion. This unit will operate in the Defrost Mode for 10 minutes or until
the Head Pressure reaches 450 PSI. The Defrost Timer determines the
length of time between Defrost Modes. The length of the Defrost Timer
can be automatically be adjusted by the Adaptive Defrost Adjustment
described in Setpoint Screen # 35. This Defrost Mode is only available
if using the VCM-X E-BUS Controller or RNE Controller and a Head
Pressure Module. A Suction Pressure Transducer is also required. This
screen only applies if using the VCM-X E-BUS Controller or RNE
Controller with a Suction Pressure Sensor, a Head Pressure Module,
and Head Pressure Transducer(s). This screen does not apply if using
the VCM-X WSHP Controller and a WSHP Module.

Description

Minimum

Default

Maximum

Heat Pump Defrost Temp

0ºF

30ºF

50ºF

Heat Pump Defrost Timer

10 Min

30 Min

90 Min

Setpoint Screen #35 - Adaptive Defrost Adj.

Setpoint

VCM-X / RNE Spts

Adaptive Defrost

Adj. Setpoint: 0 MIN

Once initiated, the Defrost Mode is active until the Head Pressure reaches
450 PSIG or until a 10 minute timer has expired. Enter a value greater
than zero to enable the Adaptive Defrost Adjustment of the Heat Pump
Defrost Timer (Screen #34). This adjustment value will be subtracted
from the Heat Pump Defrost Timer if the Defrost Mode lasts the entire
10 minutes. A proportion of this adjustment value will be added to the
Heat Pump Defrost Timer if the Defrost Mode only lasts between 8
minutes and 0 minutes. This screen only applies if using the VCM-X
Modular Controller or RNE Controller with a Suction Pressure Sensor,
a Head Pressure Module, and Head Pressure Transducer(s). This screen
does not apply if using the VCM-X WSHP Controller and a WSHP
Protection Module.

Description

Minimum

Default

Maximum

Adaptive Defrost Adj.

0 Min

0 Min

30 Min

VCM-X / RNE Setpoint Screens

Setpoint Screen #36 - Heat Wheel Defrost

VCM-X / RNE Spts

Heat Wheel Defrost

Setpoint: 32ºF

The unit will go into Heat Wheel Defrost Mode when the Outdoor Air
is below this setpoint.

Description

Minimum

Default

Maximum

Heat Wheel Defrost

0ºF

32ºF

50ºF

Setpoint Screen #37 - Internal Schedule

Optimal Start Soak Multiplier

VCM-X / RNE Spts

Internal Schedule

Optimal Start Soak

Multiplier: 0.0

The Internal Schedule Optimal Start Soak Multiplier Setpoint is a multi-
plier that if set to a number greater than 0 will be used as a multiplier for
calculating the Optimal Start Time for the HVAC unit. This multiplier
is only applied if the unit has been off for more than 24 hours. See the
VCM-X Controller Technical Guide, VCM-X Modular E-BUS Controller
Technical Guide,
or RNE Controller Technical Guide for more detailed
information regarding the Optimal Start. This multiplier is only applied
if you are using the Unit Controller Internal Schedule.

Description

Minimum

Default

Maximum

Internal Schedule Optimal

Start Soak Multiplier

0.0

0.0

5.0

Setpoint Screen #38 - Trend Log Interval

VCM-X / RNE Spts

Trend Log

Interval: 15 MIN

An internal Trend Log is constantly updated at a rate equal to this value.

Description

Minimum

Default

Maximum

Trend Log Interval

1 Min

15 Min

60 Min